Exact simulated packages
Build conditions for a 30 GW load case.
Every selector maps to one of 48 combinations generated by the canonical hourly pipeline. There is no browser-side reliability formula and no interpolation.
Read the output narrowly. Zero crossings means the chosen package stays below the assumed ceiling in all nine historical-demand replays. It is not a PJM reliability certification.
9/9
Years with a crossing
97
Worst-year hours
13.1 GW
Worst hourly gap
435.9 GWh
Worst-year energy gap
No JavaScript is required to see the baseline: nine of nine years cross the screen.
Declared mechanics
What each lever means.
Retained bridge capacity contributes 85% of nameplate in this screen. New firm capability contributes 90%. DC flexibility applies only to the incremental 30 GW and only when needed. These are assumptions exposed for sensitivity—not forecasts of accreditation or performance.